Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Comment: Added sentence that uplift forces can be calculated by the ENDUROCADD software.

...

For hold down anchor capacity, refer to manufacturer's information. Suitable hold down anchors are to be provided to resist the uplift forces calculated by the ENDUROCADD® software or as defined in Table in Tables 2-5 of Section 3.3.1 of the ENDUROWALL® Building System Design Manual.

...

For hold down anchor capacity, refer to manufacturer's information. Suitable hold down anchors are to be provided to resist the uplift forces by the ENDUROCADD® software or as defined in Tables 2-5 of Section 3.3.1 of the ENDUROWALL® Design  Building System Design Manual. 



Stud Thickness (mm)


Plate thickness (mm)

90mm sections75mm sections170mm sections1
Uplift capacity with 40x40x5mm2 washerUplift capacity with 24mm dia. bolt head or washerUplift capacity with 40x40x5mm2 washerUplift capacity with 24mm dia. bolt head or washerUplift capacity with 40x40x5mm2 washerUplift capacity with 24mm dia. bolt head or washer
0.750.7515.0kN6.0kN9.09kN4.0kN7.9kN3.5kN
1.01.021.0kN15kN18.49kN11.25kN17kN10.3kN
1.21.230.0kN19kNN/ANANANA

...

For hold down anchor capacity, refer to manufacturer's information. Suitable hold down anchors are to be provided to resist the uplift forces by the ENDUROCADD® software or as defined in in Tables 2-5 of Section 3.3.1 of the ENDUROWALL® Building System Design Manual. 

...

For hold down anchor capacity, refer to manufacturer's information. Suitable hold down anchors are to be provided to resist the uplift forces by the ENDUROCADD® software or as defined in in Tables 2-5 of Section 3.3.1 of the ENDUROWALL® Building System Design Manual.

...

For hold down anchor capacity, refer to manufacturer's information. Suitable hold down anchors are to be provided to resist the uplift forces by the ENDUROCADD® software or as defined in Tables 2-5 of Section 3.3.1 of the ENDUROWALL® Building System Design Manual. 

...

For hold down anchor capacity, refer to manufacturer's information. Suitable hold down anchors are to be provided to resist the uplift forces by the ENDUROCADD® software or as defined in in Tables 2-5 of Section 3.3.1 of the ENDUROWALL® Building System Design Manual. 

...

For hold down anchor capacity, refer to manufacturer's information. Suitable hold down anchors are to be provided to resist the uplift forces by the ENDUROCADD® software or as defined in in Tables 2-5 of Section 3.3.1 of the ENDUROWALL® Building System Design ManualManuall

Tie-down into suspended frame floor systems

...

Hold down connection - Option 4

Transfer of Racking Loads to Internal Non-Load Bearing Bracing Walls

...

Image Removed

The slotted internal wall brackets shall be installed at a maximum of1200mm centers along the non-load bearing wall.

Transfer of Racking Loads to Internal Bracing Walls - Internal Wall Perpendicular to Trusses

Image Removed

...

There are two different brackets options that may be used for this application: a slotted internal wall wall bracket, or an internal wall bracket. Either option may be used and should be installed at a maximum of 1200mm centers.

Example 1 - Slotted Bracket on Wall Running Parallel to trusses

Image Added

A slotted internal wall bracket shall be fixed to the top plate with 4 x 10-16x16 hex head fasteners and to the truss bottom chord or trimmer with 2 x 10-16x16 hex head fasteners.

Warning

It is important that the slots in the bracket allow movement between the truss and wall frame, and the fasteners are not overtightened. The truss should be able to move on the bracket in the event there is settlement. In the event that internal non-load bearing walls run parallel with roof trusses, and trimmer section shall be installed to act as a fixing point for the slotted bracket.


Example 2 - Internal Wall Bracket Perpendicular to Trusses

Image Added

Example 3 - Internal Wall Bracket Parallel with Trusses

The internal wall brackets shall be installed at a maximum of1200mm centers along the non-load bearing wall.

...

can be attached to ceiling battens.

Connecting Non-Load Bearing to Load Bearing Walls

Any of the 3 options below are suitable in non-cyclonic areas.

Option 1 - Strap

A minimum of  2 x 10-10x16 hex head fasters should be used to connect each end of the 30 x 1.0mm (min) strap.

Internal to external fixing connections (Option 2)

Image Removed

...

This option is used when there is no top nogging.

Option 2 - Angle

Image Added

Option 3 - Top nogging